Permit: T06CM05546

Parcel: 108240840


Addresses:

2492 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER HEATER NEUTRAL NOT PROPERLY IDENTIFIED
NEC 250.6A
2. HAVE UNDERSIZED EQUIPMENT GROUND THROUGHOU
NEC 250.122 B
3. PANEL DIRECTORY TO BE PERMANENT, LEGIBLE, AND CORRECT -- NEC 408.4

CORRECTLY INSTALL FIRE BELL LOCKOUT

OK TO OCCUPY
02/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
NEC 408.4 - DIRECTORY TO BE LEGIBLE ALSO
2. MAX LENGTH FOR DISPOSAL CORD IS 36" - NEC 422.16 B 1-2
MAX CORD FOR DISHWASHER IS 48" - NEC 422.16 B2-2
3. EMERGENCY LIGHTING NOT PER PLAN, NO EXTERIOR EGRESS LIGHT.
4. PROPERLY INSTALL LOCKOUT FOR FIRE BREAKER - NEC 760
5. PLANS CALL FOR A 240V WATER HEATER?
120V WATER HEATER EQUIPMENT GROUND UNDERSIZED
NEC 250.122B
NEUTRAL NOT PROPERLY IDENTIFIED - NEC 200.6
6. RECEPTACLES FOR APPLIANCE TO BE ACCESSIBLE --
NEC 422.33 B
02/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/01/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*