Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WATER HEATER NEUTRAL NOT PROPERLY IDENTIFIED NEC 250.6A 2. HAVE UNDERSIZED EQUIPMENT GROUND THROUGHOU NEC 250.122 B 3. PANEL DIRECTORY TO BE PERMANENT, LEGIBLE, AND CORRECT -- NEC 408.4 CORRECTLY INSTALL FIRE BELL LOCKOUT OK TO OCCUPY |
|
| 02/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED NEC 408.4 - DIRECTORY TO BE LEGIBLE ALSO 2. MAX LENGTH FOR DISPOSAL CORD IS 36" - NEC 422.16 B 1-2 MAX CORD FOR DISHWASHER IS 48" - NEC 422.16 B2-2 3. EMERGENCY LIGHTING NOT PER PLAN, NO EXTERIOR EGRESS LIGHT. 4. PROPERLY INSTALL LOCKOUT FOR FIRE BREAKER - NEC 760 5. PLANS CALL FOR A 240V WATER HEATER? 120V WATER HEATER EQUIPMENT GROUND UNDERSIZED NEC 250.122B NEUTRAL NOT PROPERLY IDENTIFIED - NEC 200.6 6. RECEPTACLES FOR APPLIANCE TO BE ACCESSIBLE -- NEC 422.33 B |
|
| 02/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/01/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |