Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/12/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE PROPERLY SIZED EQUIPEMENT GROUND TO GROUND ALL BOXES AND EQUIPMENT - NEC 314.4, 250.122 2. BOXES NOT MOUNTED PROPERLY - NEC 314.23B 3. HAVE OVERFILLED BOXES - NEC 314.16 4. FINISH ALL CEILING WIRING INCLUDING LOW VOLTAGE BEFORE INSPECTION. |