Permit: T06CM05534

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM05534

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/25/2007 PLUMBING - FINAL Approved
05/24/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
05/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. THE POINT OF VENT MAY NOT BE BELOW THE TRAP WEIR
2. THE BACKFLOW DEVICE APPROVED FOR ICE MAKERS IS A WATTS 007 OR EQUAL.
05/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
ALL FLOOR SINKS TO HAVE GRATES AND STRAINERS
REMOVE ALL CHROME PLATED CLEANOUT COVERS
CLEANOUTS TO BE EXTENDED TO FACE OF WALL,
COUNTER SUNK TAPPED PLUGS, ETC.
CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE. REVIEW ALL CORRECTIONS LEFT PREVIOUSLY.
05/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CAULK AND SEAL ALL FIXTURES
2. JANITOR SINK REQUIRES ACCESSIBLE CLEANOUT
3. FINISH INSULATION ON HOT PIPING
4. ALL CLEANOUTS TO BE EXTENDED TO THE WALL, WITH COUNTER.
5. SUNK TAPPED PLUG W/C.P COVER AND 5/16" SCREW
6. GRATES AND STRAINERS
7. INDIRECT WASTE PIPING MAY NOT BE COMBINED
8. OVER 5' IN LENGTH TO BE DIRECTLY TRAPPED
9. REQUIRE FULL 1" AIR GAP AT DIPPER WELLS
10. REQUIRE BACKFLOW PROTECTION AT ICE MAKER
11. PRESSURE GAUGE AND THERMOMETER ON WH