Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05534

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STILL HAVE SEVERAL LOCATIONS WHERE EMT IS NOT STRAPPED WITHIN 36" OF ENCLOSURES.
2. NEED TO INSTALL K.O BLANKS ON SEVERAL BOXES
3. STILL HAVE OVERFILLED BOXES (USE ONLY 1 EXTENSION BOX WHEN OVERFILLED)
4. STILL HAVE DEMO (RACEWAYS, BOXES, ETC) TO DO IN CEILING.

THERE WILL BE A FEE IF NOT CORRECT NEXT TIME
BOX FILL - NEC 314.16
MAX 9 #12'S IN SHALLOW 4 SQ
MAX 13 #12'S IN DEEP 4 SQ
GROUNDS ALL COUNT AS 1
05/15/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OVERFILLED BOXES THROUGHOUT
2. DEMO UN USE RACEWAYS/WIRING
3. ALL LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED/NOT LAYING ON GRID.
4. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES
5. M.C TO BE SECURED WITHIN 12" OF TERMINATIONS.