Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM05534
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/16/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. STILL HAVE SEVERAL LOCATIONS WHERE EMT IS NOT STRAPPED WITHIN 36" OF ENCLOSURES. 2. NEED TO INSTALL K.O BLANKS ON SEVERAL BOXES 3. STILL HAVE OVERFILLED BOXES (USE ONLY 1 EXTENSION BOX WHEN OVERFILLED) 4. STILL HAVE DEMO (RACEWAYS, BOXES, ETC) TO DO IN CEILING. THERE WILL BE A FEE IF NOT CORRECT NEXT TIME BOX FILL - NEC 314.16 MAX 9 #12'S IN SHALLOW 4 SQ MAX 13 #12'S IN DEEP 4 SQ GROUNDS ALL COUNT AS 1 |
|
05/15/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED BOXES THROUGHOUT 2. DEMO UN USE RACEWAYS/WIRING 3. ALL LOW VOLTAGE WIRING TO BE PROPERLY SUPPORTED/NOT LAYING ON GRID. 4. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES 5. M.C TO BE SECURED WITHIN 12" OF TERMINATIONS. |