Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T06CM05523
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
12/05/2006 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 20 FOOT REBAR REQUIRED 3" ABOVE BOTTOM OF FOOTING AND GROUND WIRE CANNOT BE INSTALLED WITH A HOSE CLAMP 2) INSTALL TWO GROUND ROD OR REPAIR AND RESCHEDULE |