Permit Number - T06CM05523

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/31/2007 FRAMING Approved IVRS - Inspection :*
1) PORCH #1 HAS OSB OK J. RIVA
01/25/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 2" CLEARANCE BETWEEN STUCCO WEEP SCREED AND FRONT PORCH AND REAR PORCH
2) NO DWV WATER TEST
3) 6'-8" CLEARANCE REQUIRED OVER POWDER ROOM TOILET PER IRC 305.1 EXCEPT ?
4) HOLDOWN NUTS LOOSE BY ENTRY
5) HTT16 HOLDOWNS REQUIRED
6) RISE ON 4TH STEP EXCEEDS 7 3/4"
7) STAIR MUST BE 36" WIDE FINISHED
8) STAIR PONY WALL MUST SUPPORT 200 LB SIDE LOAD
9) BEDROOM 2 DUCT LOCATION
10) MISSING ENTRY LIGHT
11) NAIL PROTECT WIRES AND PLUMBING
12) PROVIDE BLOCKS FOR DRYWALL SHEAR ?
01/24/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SHANNON