Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM05523
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2007 | FRAMING | Approved | IVRS - Inspection :* 1) PORCH #1 HAS OSB OK J. RIVA |
|
01/25/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 2" CLEARANCE BETWEEN STUCCO WEEP SCREED AND FRONT PORCH AND REAR PORCH 2) NO DWV WATER TEST 3) 6'-8" CLEARANCE REQUIRED OVER POWDER ROOM TOILET PER IRC 305.1 EXCEPT ? 4) HOLDOWN NUTS LOOSE BY ENTRY 5) HTT16 HOLDOWNS REQUIRED 6) RISE ON 4TH STEP EXCEEDS 7 3/4" 7) STAIR MUST BE 36" WIDE FINISHED 8) STAIR PONY WALL MUST SUPPORT 200 LB SIDE LOAD 9) BEDROOM 2 DUCT LOCATION 10) MISSING ENTRY LIGHT 11) NAIL PROTECT WIRES AND PLUMBING 12) PROVIDE BLOCKS FOR DRYWALL SHEAR ? |
|
01/24/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER SHANNON |