Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/26/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE METAL BOXES ON ARMORED CABLE. CHECK ENTIRE SPACE. SWITCHES , RECEPT AND LIGHT FIXTURES 2) OPEN JUNCTION BOXES IN CEILING. SECURE AND SUPPORT JUNCTION BOXES 3) INSTALL CONNECTORS ON ARMORED CABLE ENTERING JUNCTION BOXES 4) TIE WIRE RECESSED LIGHTS, EXITS AND TRACK LIGHTS 5) GROUND ALL METAL BOXES 6) USE APPROPRIATE COLORED WIRE AT RECPT, SWITCHES AND JUNCTION BOXES. BLACK, RED AND BLUE 120/240 V, BROWN, ORANGE AND YELLOW 277/480 V, WHITE NEUTRAL, GREEN GROUND 7) SECURE AND SUPPORT WIRING IN CEILING 8) CANNOT HAVE OPEN CONDUCTORS ? IN CEILING 9) REMOVE ALL OLD/ABANDONED WIRING IN CEILING 10) THIS MAY NOT BE COMPLETE LIST 11) INSTALL JUNCTION BOXES ON FEEDS TO TRACK LIGHT |
|
| 03/08/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |