Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05517
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/12/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
09/06/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - DRAIN CONNECTION TO COIL IS CROSS-THREADED - DO NOT USE DUCT TAPE TO SUPPORT REFER LINES - REPLACE THE FLATTENED CONDENSATE TRAP - PROVIDE A PERMIT FOR NEW WATER HEATER - DO NOT USE COPPER FLEX ON T&P DRAIN - CAP OFF THE OLD FURNACE VENT ON THE ROOF - DO NOT USE WHITE WIRE IN THE ELEC. DISCONNECT |
|
11/29/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* NO ACCESS FOR INSPECTION NO ANSWER AT DOOR DISCONNECT FOR AC MUST BE BRACED |
|
11/17/2006 | MECHANICAL - FINAL | Cancelled | CANCELLED PER COTY OF APPLE PLUMBING & COOLING #572-4372 |