Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* AIR BALANCE OK OK FOR FINAL |
|
| 03/15/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AIR BALANCE REPORT 2. 3/8" I.D X 24" GAS FLEX CONNECTORS NOT ADEQUATE FOR 90,000 BTU. 3. PROVIDE MIN. R8 DUCT LINER IN EXPOSED DUCT ON ROOF. 4. PROVIDE THE PROPER GAS ISOMETRIC DRAWING ON PLANS. 5. PROVIDE MANIFOLD IF NECESSARY & A PRESSURE TEST. 6. ALL FRESH AIR INTAKES MUST BE FILTERED. MISSING SCREEN! 7. PROVIDE SERVICE RECEPTACLES. 8. TIGHTEN ALL LOOSE ELEC. CONNECTIONS. 9. RELOCATE DISCONNECTS 10. GAS PIPE BLOCKING ACCESS TO A/C 2 |
|
| 02/14/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* TEMP C OF O PHASE 1 OK TO OCCUPY ROOM 105 |