Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/23/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
AIR BALANCE OK
OK FOR FINAL
03/15/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AIR BALANCE REPORT
2. 3/8" I.D X 24" GAS FLEX CONNECTORS NOT ADEQUATE
FOR 90,000 BTU.
3. PROVIDE MIN. R8 DUCT LINER IN EXPOSED DUCT ON ROOF.
4. PROVIDE THE PROPER GAS ISOMETRIC DRAWING ON PLANS.
5. PROVIDE MANIFOLD IF NECESSARY & A PRESSURE TEST.
6. ALL FRESH AIR INTAKES MUST BE FILTERED. MISSING SCREEN!
7. PROVIDE SERVICE RECEPTACLES.
8. TIGHTEN ALL LOOSE ELEC. CONNECTIONS.
9. RELOCATE DISCONNECTS
10. GAS PIPE BLOCKING ACCESS TO A/C 2
02/14/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TEMP C OF O PHASE 1
OK TO OCCUPY ROOM 105