Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED PER 250.122 OK TCO |
|
| 03/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OUTLET PLATE STRIPED - SECURE TO DEVICE 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING. 3. USE CORRECT COLOR CONDUCTORS IN RACEWAYS 4. TIGHTEN LOOSE FITTINGS 5. REVISE PLANS FOR WATER HEATER - CIRCUIT & LOADS AND 220V DRYER. 6. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 7. EXIT LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12 8. NEED ROOF MAINTENANCE RECEPTACLE 9. TIGHTEN LOOSE FITTINGS 10. WHY DO WE HAVE HIGH LEG MARKINGS ON CONDUCTOR. |
|
| 02/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TCO OFFICE 105 ONLY |