Permit: T06CM05516

Parcel: 13322500G


Addresses:

7109 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED PER 250.122 OK TCO
03/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OUTLET PLATE STRIPED - SECURE TO DEVICE
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING.
3. USE CORRECT COLOR CONDUCTORS IN RACEWAYS
4. TIGHTEN LOOSE FITTINGS
5. REVISE PLANS FOR WATER HEATER - CIRCUIT & LOADS AND 220V DRYER.
6. BREAKER TO BE LISTED FOR USE BY MANUFACTURE
7. EXIT LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12
8. NEED ROOF MAINTENANCE RECEPTACLE
9. TIGHTEN LOOSE FITTINGS
10. WHY DO WE HAVE HIGH LEG MARKINGS ON CONDUCTOR.
02/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TCO OFFICE 105 ONLY