Permit: T06CM05516

Parcel: 13322500G


Addresses:

7109 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/27/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/06/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK PHASE I TO TILE
02/02/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH VDV CABELING-NO SECURING DONE
2) OVER 6' LENGTHS NOT SUPPORTED
01/26/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6
2. SUPPORT WIRE NEEDED - OPPOSITE CORNERS

NOTE: BOXES MORE THAN 1/4" FROM BOX TO SURFACE MAY NEED APPROVED EXTENDER RINGS 314.20
GROUND FLOOR BOXES