Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM05504
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
01/04/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HAND SINK MAY NOT BE INDIRECTLY CONNECTED AND IT IS NOT EVEN ON THE PLAN. 2. 009 BACKFLOW PREVENTORS REQUIRE FULL SIZE TO DEVICE PROPERLY SUPPORTED AND DRAINED. 3. 2 COMPARTMENTS OF 3 COMP SINK TO BE DIRECTLY CONNECTED. |
|
01/03/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* (EACH WATER SUPPLIED DEVICE TO HAVE BACKFLOW PROTECTION) 1. INDIRECT WASTE PIPING MAY NOT BE COMBINED. 2. INDIRECT WASTE PIPING OVER FIVE FEET IN DEVELOPED LENGTH TO BE DIRECTLY TRAPPED. 3. PITCHER RINSER SINK HAS SUBMERGED INLET WITH NO BACKFLOW PROTECTION. 4. GRATES AND STRAINERS 5. ONLY ONE SLIP NUT OUTLET SIDE OF TRAP 6. SINKS REQUIRE CLEAN-OUTS INSPECTION STOPPED |