Permit: T06CM05504


Addresses:

802 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM05504

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/04/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAND SINK MAY NOT BE INDIRECTLY CONNECTED AND IT IS NOT EVEN ON THE PLAN.
2. 009 BACKFLOW PREVENTORS REQUIRE FULL SIZE TO DEVICE PROPERLY SUPPORTED AND DRAINED.
3. 2 COMPARTMENTS OF 3 COMP SINK TO BE DIRECTLY CONNECTED.
01/03/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
(EACH WATER SUPPLIED DEVICE TO HAVE
BACKFLOW PROTECTION)

1. INDIRECT WASTE PIPING MAY NOT BE COMBINED.
2. INDIRECT WASTE PIPING OVER FIVE FEET IN DEVELOPED LENGTH TO BE DIRECTLY TRAPPED.
3. PITCHER RINSER SINK HAS SUBMERGED INLET WITH NO BACKFLOW PROTECTION.
4. GRATES AND STRAINERS
5. ONLY ONE SLIP NUT OUTLET SIDE OF TRAP
6. SINKS REQUIRE CLEAN-OUTS

INSPECTION STOPPED