Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05503
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/04/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) TESTED DUCT SMOKE DETECTORS 2) STILL NEED LETTER FROM ENGINEER OR OWNER 3) SEE BLDG INSPECTOR FOR TEMP C OF O |
|
02/01/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - AUDIBLE & VISIBLE ALARMS NOT WORKING - PROVIDE A LETTER FROM ENGINEER TO ACCEPT GOODMAN EQUIPMENT - PLANS SPEC. TRANE OR ICP - DO NOT USE MALE METAL FITTING INTO PLASTIC FEMALE - SCRATCH OFF BOX NEXT TO PROPER HEAT STRIP AND FUSE ACCORDINGLY, IF NONE SCRATCH OFF NEXT TO NONE. |
|
01/31/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - STILL NEED TO SEE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTOR AS PER 2006 IMC SECTION 606.4.1 - DO NOT USE METAL MALE PIPE THREADS INTO FEMALE PLASTIC ON CONDENSATE DRAIN PAN - 30 AMP FUSE EXCEEDS MAX. FUSE SIZE - PROVIDE REDUCING WASHER AT ELEC. CONNECTION TO NEW A/C UNIT. TIGHTEN ALL LOOSE FITTINGS. |
|
01/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - FINISH CONDENSATE PIPING ON ROOF - PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS - PROVIDE AIR BALANCE REPORT |