Permit: T06CM05503

Parcel: 110113620

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM05503

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/04/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) TESTED DUCT SMOKE DETECTORS
2) STILL NEED LETTER FROM ENGINEER OR OWNER
3) SEE BLDG INSPECTOR FOR TEMP C OF O
02/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- AUDIBLE & VISIBLE ALARMS NOT WORKING
- PROVIDE A LETTER FROM ENGINEER TO ACCEPT GOODMAN EQUIPMENT
- PLANS SPEC. TRANE OR ICP
- DO NOT USE MALE METAL FITTING INTO PLASTIC FEMALE
- SCRATCH OFF BOX NEXT TO PROPER HEAT STRIP AND FUSE ACCORDINGLY, IF NONE SCRATCH OFF NEXT TO NONE.
01/31/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- STILL NEED TO SEE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTOR AS PER 2006 IMC SECTION 606.4.1
- DO NOT USE METAL MALE PIPE THREADS INTO FEMALE PLASTIC ON CONDENSATE DRAIN PAN
- 30 AMP FUSE EXCEEDS MAX. FUSE SIZE
- PROVIDE REDUCING WASHER AT ELEC. CONNECTION TO NEW A/C UNIT. TIGHTEN ALL LOOSE FITTINGS.
01/30/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- FINISH CONDENSATE PIPING ON ROOF
- PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS
- PROVIDE AIR BALANCE REPORT