Permit: T06CM05503

Parcel: 110113620

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM05503

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/23/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
- DWV W/TEST TO TIE IN POINT OK
- DOMESTIC WATER PIPING OK BUT IS NOT INSULATED TO PLAN SPECS PROVIDE LETTER OF APPROVAL
01/18/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ADD ROUGH SOIL TO INSPECTION CARD

- SEC. 1014.1.3 DOES NOT ALLOW A DISHWASHER TO BE CONNECTED TO ANY GREASE INTERCEPTOR.
- ALSO, SEE SEC. 1014.2 FOR FLOW CONTROL INSTALLATION
- VENT TAKE OFF FOR FS AT ICE MAKER
SHALL BE ABOVE FLOW LINE OF FIXTURE.
USE A 1/6TH BEND OR EQUAL
- TRAP ARM DISTANCE IS MIN. 2X DIA.