Permit: T06CM05503

Parcel: 110113620

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/31/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLUGS AND EQUIPMENT TO BE ACCESSIBLE
2. ICE MACHINE NOT CORD & PLUG APPLIANCE -
NEED DISCONNECTING MEANS
3. "EXISTING" IS NOT A CIRCUIT DESCRIPTION -
LABEL ALL BREAKERS
4. EM EXIT LIGHTING TO BE ON AREA SERVED - 700.12
5. SUPPORT M/C CABLES TO CANS IN HANGING CEILINGS
6. APPROVED EXTENDER RINGS AT COMBUSTIBLES - BATHROOMS
7. FINISH VDV CABLING
01/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VDV CABELING TO BE PER 725.3 + 6, 800.3 + 6 AND 300.11
2) BROKEN M/C ARMOR
3) OK 2 X 4'S
01/23/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection 1. PROTECT VDV CABLING FROM SHARP METAL EDGES - 725.6
2. ALL DRYWALL OVER ELECTRIC TO BE INSTALLED
3. DEVICES 8' AND BELOW TO BE INSTALLED & PLATED
4. ADD TEMP POWER TO PERMIT 02062 - NO BOND
01/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS - STUD FRAMED
OK HARD CEILING
OK FLOOR JUNCTION BOX

1. USE PULL SECTION FOR SES
2. TIGHTEN LOOSE FITTINGS
3. STRAP M/C CABLE WITHIN 12" OF CANS

RECEIVED CHECK #10201 FOR $150.00