Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05503
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLUGS AND EQUIPMENT TO BE ACCESSIBLE 2. ICE MACHINE NOT CORD & PLUG APPLIANCE - NEED DISCONNECTING MEANS 3. "EXISTING" IS NOT A CIRCUIT DESCRIPTION - LABEL ALL BREAKERS 4. EM EXIT LIGHTING TO BE ON AREA SERVED - 700.12 5. SUPPORT M/C CABLES TO CANS IN HANGING CEILINGS 6. APPROVED EXTENDER RINGS AT COMBUSTIBLES - BATHROOMS 7. FINISH VDV CABLING |
|
01/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VDV CABELING TO BE PER 725.3 + 6, 800.3 + 6 AND 300.11 2) BROKEN M/C ARMOR 3) OK 2 X 4'S |
|
01/23/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1. PROTECT VDV CABLING FROM SHARP METAL EDGES - 725.6 2. ALL DRYWALL OVER ELECTRIC TO BE INSTALLED 3. DEVICES 8' AND BELOW TO BE INSTALLED & PLATED 4. ADD TEMP POWER TO PERMIT 02062 - NO BOND |
|
01/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS - STUD FRAMED OK HARD CEILING OK FLOOR JUNCTION BOX 1. USE PULL SECTION FOR SES 2. TIGHTEN LOOSE FITTINGS 3. STRAP M/C CABLE WITHIN 12" OF CANS RECEIVED CHECK #10201 FOR $150.00 |