Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM05499
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
01/11/2007 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER |
|
01/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING WIND BRACE-1ST FLOOR SOUTH SIDE 2) 1ST AND 2ND FLOOR RSP4'S NEED TO LINE UP 3) HOLDOWNS ON GARAGE SIDEWALLS IN WRONG PLACE-TO BE UNDER GLU-LAM PER PLAN 4) TWO HOLDOWN STRAPS REQUIRED ON SHEARWALL OVER GARAGE 5) SW3 AT M. CLOSET 2ND FLOOR TO EXTEND PAST POST PER PLAN AND NEEDS HOLDOWN STRAP PER PLAN 6) 8D TECKO NAILS NOT RATED THROUGH SHEARTHING 7) COLUMN RAISING AT PATIO 8) STOPPED INSPECTION |