Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSTALL CONNECTOR ON WIRE TO FAN 2) PREVIOUS INSPECTION ITEMS CORRECTED 3) OK WALLS AND CEILINGS |
|
| 05/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. NO ACCESS TO UNIT 2. NEED LADDER TO INSPECT SERVICE |
|
| 05/21/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INTERIOR 1. NEED TO USE PROPER CRIMP TO ON CRIMP SLEEVES NOT JUST SQUEEZED FLAT -- NEC 110.3B 2. HAVE OVERFILLED BOXES -- NEC 314.16 3. WHERE IS RANGE RECEPTACLE? WIRE, FAN SERVICE 1. BOND MAST, SERVICE RACEWAYS 2. BOND GUTTER 250.92, 250.102 (WITH PROPER SIZE BONDING CONDUCTOR) SERVICE ENERGIZED BEFORE APPROVAL |