Permit: T06CM05491

Parcel: 108253370


Addresses:

2026 E RIVER RD 5


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM05491

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/26/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/08/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ADD STRAPS TO VERTICAL PIPING 2ND FLOOR
2. NEED TO SEE FLANGES AFTER FLOOR/TILE
3. OK TO COVER ALL AREAS
01/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
POST YOUR ADDRESS
PROVIDE A "FIRM BASE" UNDER CLOSET FLANGES
TEST SHOWERS TO OVERFLOW LEVEL AND TUBS
SUPPORT HORIZONTAL SECTIONS OF VENTS CLOSE TO VTR
PROVIDE A DRAIN FOR WH PAN
ABS NOT UNDER TEST
12/19/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO PRE-ROCK FIRST FLOOR
12/05/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
YOU CANNOT PRE-ROCK UNTIL THE PLUMBER HAS COMPLETED AND TESTED HIS WORK - CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE
12/03/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. NOT READY
NOTE: SUPPORT VERTICAL PIPE
HORIZ X HORIZ DRAINAGE, (AND VENTING BELOW FLOOD RIM) TO BE A SWEEP

NO TEST ON ABS