Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM05491
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/08/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ADD STRAPS TO VERTICAL PIPING 2ND FLOOR 2. NEED TO SEE FLANGES AFTER FLOOR/TILE 3. OK TO COVER ALL AREAS |
|
| 01/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* POST YOUR ADDRESS PROVIDE A "FIRM BASE" UNDER CLOSET FLANGES TEST SHOWERS TO OVERFLOW LEVEL AND TUBS SUPPORT HORIZONTAL SECTIONS OF VENTS CLOSE TO VTR PROVIDE A DRAIN FOR WH PAN ABS NOT UNDER TEST |
|
| 12/19/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO PRE-ROCK FIRST FLOOR |
|
| 12/05/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* YOU CANNOT PRE-ROCK UNTIL THE PLUMBER HAS COMPLETED AND TESTED HIS WORK - CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE |
|
| 12/03/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NOT READY NOTE: SUPPORT VERTICAL PIPE HORIZ X HORIZ DRAINAGE, (AND VENTING BELOW FLOOD RIM) TO BE A SWEEP NO TEST ON ABS |