Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05491
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/07/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR ELECTRICAL COVER |
|
| 10/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED |
|
| 10/02/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROPER CRIMP TOOL FOR CRIMP SLEEVES 2. HAVE OVERFILLED WIRE NUTS 3. PIGTAIL NEUTRALS ON 3-WIRE HOME RUNS 4. MISSING NAIL PLATES - SEVERAL LOCATIONS 5. REMOVE BONDING SCREWS IN SUB-PANELS 6. CHECK RECEPTACLE LAYOUT - 210.52 MAX 6' FROM BROKEN WALL LINE MAX 12' BETWEEN RECEPTACLES COUNTER MAX 24" FROM BROKEN COUNTER ALONG WALL LINE AND BETWEEN RECEPTACLES. |