Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM05490
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/23/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL WYE BRANCHES TO BE INSULATED WITH FOIL FACED DUCT WRAP - 200, 201, 204 MUST USE APPROVED NAIL PLATES 203 - EF DUCT |
|
| 10/19/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 205 - NEED SCREWS IN E.F DUCT PATCH HOLE IN DUCT USE PRIMER ON CPVC CONDENSATE PIPE 202 - NEED SCREWS IN E.F DUCT CONDENSATE PIPING NOT CONNECTED. USE PRIMER ON ALL PVC PIPE 203 - CONDENSATE NOT TIED IN, SCREWS IN E.F DUCT PANDUITS NOT APPROVED HANGER E.F DUCTING WYE FITTING IMPROPERLY INSTALLED, NOT MECHANICALLY FASTENED - PROVIDE MANUFACTURES AND UL APPROVAL FOR TIE WRAPS IN H.V.A.C APPLICATION |
|
| 08/17/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK 1ST FLOOR |