Permit: T06CM05490

Parcel: 108253250


Addresses:

2018 E RIVER RD 4

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/24/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/23/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALL WYE BRANCHES TO BE INSULATED WITH FOIL FACED DUCT WRAP - 200, 201, 204

MUST USE APPROVED NAIL PLATES 203 - EF DUCT
10/19/2007 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
205 - NEED SCREWS IN E.F DUCT
PATCH HOLE IN DUCT
USE PRIMER ON CPVC CONDENSATE PIPE

202 - NEED SCREWS IN E.F DUCT
CONDENSATE PIPING NOT CONNECTED.
USE PRIMER ON ALL PVC PIPE

203 - CONDENSATE NOT TIED IN, SCREWS IN E.F DUCT
PANDUITS NOT APPROVED HANGER
E.F DUCTING WYE FITTING IMPROPERLY INSTALLED, NOT MECHANICALLY FASTENED
- PROVIDE MANUFACTURES AND UL APPROVAL FOR TIE WRAPS IN H.V.A.C APPLICATION
08/17/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK 1ST FLOOR