Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05489
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* OK ROOF TOP UNIT #202: MULTI WIRE BRANCH CKT'S TO TERMINATE ON SEPERATE PHASES REVISE PANEL DIRECTORY MINIMUM #10 GROUND TO WATER HEATER ------------------------------------------------------------------------------------------------- UNIT #201: KITCHEN GFI NOT TRIPPING NEED #10 GROUND TO WATER HEATER DRYER RECEPTACLE TO BE 30 AMP |
|
| 10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY ON ROOF 1. STRAP FLEX 2. IDENTIFY WHITE USED AS HOT 3. USE METAL IDENTIFICATION LABELS |
|
| 10/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES AND REMARK PANEL DIRECTORIES GO THROUGH ALL UNITS BEFORE CALLING IN FOR FINAL HAVE SEVERAL PROBLEMS THROUGHOUT |
|
| 09/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 - FLUSH AT COMBUSTIBLES 2. PROPERLY INSTALL GROUND CONDUCTOR UNDER SCREWS. TERMINAL ENDS NEEDED FOR STRANDED CONDUCTOR 3. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 110.12 |