Permit: T06CM05489

Parcel: 108253130


Addresses:

2024 E RIVER RD 3


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05489

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
OK ROOF TOP
UNIT #202: MULTI WIRE BRANCH CKT'S TO TERMINATE ON SEPERATE PHASES
REVISE PANEL DIRECTORY
MINIMUM #10 GROUND TO WATER HEATER
-------------------------------------------------------------------------------------------------
UNIT #201: KITCHEN GFI NOT TRIPPING
NEED #10 GROUND TO WATER HEATER
DRYER RECEPTACLE TO BE 30 AMP
10/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY

ON ROOF
1. STRAP FLEX
2. IDENTIFY WHITE USED AS HOT
3. USE METAL IDENTIFICATION LABELS
10/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES AND REMARK PANEL DIRECTORIES

GO THROUGH ALL UNITS BEFORE CALLING IN FOR FINAL
HAVE SEVERAL PROBLEMS THROUGHOUT
09/28/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 - FLUSH AT COMBUSTIBLES
2. PROPERLY INSTALL GROUND CONDUCTOR UNDER SCREWS. TERMINAL ENDS NEEDED FOR STRANDED CONDUCTOR
3. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 110.12