Permit: T06CM05489

Parcel: 108253130


Addresses:

2024 E RIVER RD 3


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05489

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
07/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONTRACTOR WILL RELOCATE SMOKE DETECTORS AND START WIRING LIVING ROOM RECEPTACLES FROM A CKT OTHER THAN KITCHEN COUNTER RECEPTACLES CKTS.
OK ELECTRICAL COVER FIRST FLOOR.
07/18/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SMOKE DETECTORS TO BE BETWEEN 4" & 12" FROM CEILINGS
2. KITCHEN COUNTER RECEPTACLES NOT TO SERVE LIVING ROOM - RECEPTACLES OR OTHER LOADS NOT ALLOWED BY NEC 210.52
3. BAD MUD RING SE UNIT BEDROOM

PROVIDE S.D INSTALL SHEET
07/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND LEVEL COVER
06/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE OVER FILLED J-BOXES, CORRECT AS NEEDED NEC 314.16
2) PIG TAIL NEUTRALS ON 3 WIRE HOME RUNS NEC 300.13 B
3) RECEPTACLES NOT PROPERLY SPACED NEC 210.52 A 1, 2
4) FINISH PLUMBING, MECHANICAL INSTALLATION
5) ADD NAIL PLATES AS NEEDED NEC 300, 4 A
6) SUPPORT LOW VOLTAGE WIRING IN CEILINGS AS NEEDED