Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05489
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/27/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 07/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONTRACTOR WILL RELOCATE SMOKE DETECTORS AND START WIRING LIVING ROOM RECEPTACLES FROM A CKT OTHER THAN KITCHEN COUNTER RECEPTACLES CKTS. OK ELECTRICAL COVER FIRST FLOOR. |
|
| 07/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SMOKE DETECTORS TO BE BETWEEN 4" & 12" FROM CEILINGS 2. KITCHEN COUNTER RECEPTACLES NOT TO SERVE LIVING ROOM - RECEPTACLES OR OTHER LOADS NOT ALLOWED BY NEC 210.52 3. BAD MUD RING SE UNIT BEDROOM PROVIDE S.D INSTALL SHEET |
|
| 07/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND LEVEL COVER |
|
| 06/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE OVER FILLED J-BOXES, CORRECT AS NEEDED NEC 314.16 2) PIG TAIL NEUTRALS ON 3 WIRE HOME RUNS NEC 300.13 B 3) RECEPTACLES NOT PROPERLY SPACED NEC 210.52 A 1, 2 4) FINISH PLUMBING, MECHANICAL INSTALLATION 5) ADD NAIL PLATES AS NEEDED NEC 300, 4 A 6) SUPPORT LOW VOLTAGE WIRING IN CEILINGS AS NEEDED |