Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM05484

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/26/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/07/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE LISTING FOR USE OF 3" FLANGE INSIDE 4" PIPE
- SUPPORT FLANGE ON FIRM BASE AND SECURE TO FLOOR W/SCREWS
- UPC SECTIONS 316.3.1, 704.4.4
- UPC IS #9 SEC 314.2 PG 342
08/08/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CODE REQUIRES FLANGES TO SET ON FF AND SECURED
07/03/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
VENT FOR P-3 MISSING SAFETY PLATE
INSTALL HANGER ON WATER SERVICE PIPING ABOVE CEILING
07/02/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER WALLS
2. DWV SUPPORTS OK
3. SUPPORT WATER PIPING AT CHANGES OF DIRECTION AND IN A MANNER THAT WILL ALLOW VALVE TO OPEN FULLY.
4. RECALL FOR CLOSET FLANGE INSP. AFTER FLOORING IS FINISHED.
06/20/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL SAFETY PLATES AT 4" VENTS
LAV CARRIERS AND SUPPORT ON OVERHEAD PVC
06/19/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TEST THRU ROOF OK
SUPPORT HORIZONTAL PLASTIC
COMPLETE WATER
FASTEN CLOSET FLANGES TO FLOOR, MUST BE INSTALLED ABOVE FINISHED FLOOR.