Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED LIGHT FOR PANEL IN CLOSET -- NEC 110.26D 2. FINISH DISHWASHER/DISPOSAL WIRING 3. PANEL DIRECTORY NOT PROPERLY IDENTIFIED - NEC 408.4 4. HAVE SEVERAL LOOSE RECEPTACLES TIGHTEN AS NEEDED NEC 406.4 DISP. CORD - 18"-36" USE CONNECTORS ON EACH DISH CORD 48" MAX |