Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05483
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS I WILL REQUIRE A LADDER FOR CEILING INSPECTION IN CEILING CHECK FOR FOLLOWING ALL FIXTURES HAVE SUPPORT WIRES AND SECURED TO GRID, CHECK BOX FILL AND BOX GROUNDING, NO OPEN WIRING, FINISH ALL LOW VOLTAGE WIRING, ETC. |
|
01/12/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 12:56 PM DOOR IS LOCKED |
|
01/10/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* REVISE PERMIT TO SHOW CORRECT SPACE NUMBER |