Permit: T06CM05483

Parcel: 108214280

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM05483

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2007 FRAMING Approved IVRS - Inspection :*
OK TO SHEETROCK ONE SIDE THROUGHOUT
01/12/2007 FRAMING Cancelled IVRS - RI canceled
01/10/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1. APPROVED PLANS DO NOT SHOW PARTITION WALL
IN ROOM #205 - ARCHITECT NEEDS TO VERIFY CHANGE.
2. ROOM #214 INSTALL KICKERS AS PER DETAIL "A" ON PAGE 4 OF PLANS - DO NOT ANCHOR STUDS TO CEILING GRID SYSTEM.
3. RECALL WHEN EXISTING ENTRY DOOR IS MOVED AS PER PLANS AND SOUTH WALL OF ROOM #212 HAS BEEN ERECTED.