Inspection History Details
Permit: T06CM05476
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CORRECTION MADE OK OK TO COVER ALL AREAS |
|
| 04/27/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TELL THE PLUMBER THAT A TRAP ARM MAY NOT EXCEED 3'6" FROM TRAP WEIR TO POINT OF VENT. ALSO, POINT OF VENT MAY NOT BE BELOW TRAP WEIR |
|