Permit: T06CM05449

Parcel: 10511040D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM05449

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
11/23/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER WALLS
2) RECEIVED LETTER ALLOWING ABS, ARMAFLEX AND TYPE "L"
11/22/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1.UNLISTED HANGERS ARE NOT APPROVED.
REVIEW 301 2003 UPC LISTED MATERIALS.
2. OK TO INSULATE HOT PER PLUMBING SPEC 2- PRODUCTS
2.2.2.7 PIPE INSULATION.
3. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN 4' BETWEEN HANGERS.
4. OK FOR DRYWALL IN AREAS THAT DON'T HAVE HOT PIPING.
11/20/2006 PLUMBING - INTERMEDIATE Not ready for Inspection PLAN CALLS FOR CAST IRON - INSTALLED IS ABS
FEMALED THREADED ABS FITTINGS NOT PERMITTED IN ACCESSIBLE LOCATION.
BLAKE TEE NOT PERMITTED IN ITS BACK.
HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION
TO BE A SWEEP.
PLAN CALLS FOR TYPE "K" COPPER INSTALLED IS TYPE "L".
RESCHEDULE FOR MONDAY.