Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05449
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NOTE: INSTALL PROPER SIZED GROUND TAILS IN WATER HEATER J-BOXES NEC 250.122 |
|
12/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BRANCH CKT TO WATER HEATER UNDERSIZED - NEC 422.13 2. IDENTIFY WHITE USED AS HOT -- NEC 200 3. NUMBER BREAKERS IN PANEL -- NEC 408.4 4. PLANS CALL FOR COMPLIANCE WITH NEC 517.13 BUT INSTALLATION DOES NOT COMPLY (CHECK WITH ARCHITECT). |