Permit: T06CM05449

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05449

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
NOTE: INSTALL PROPER SIZED GROUND TAILS IN WATER HEATER J-BOXES
NEC 250.122
12/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRANCH CKT TO WATER HEATER UNDERSIZED - NEC 422.13
2. IDENTIFY WHITE USED AS HOT -- NEC 200
3. NUMBER BREAKERS IN PANEL -- NEC 408.4
4. PLANS CALL FOR COMPLIANCE WITH NEC 517.13 BUT INSTALLATION DOES NOT COMPLY (CHECK WITH ARCHITECT).