Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EQUIPMENT GROUNDING CONDUCTOR TO BE GREEN OR BARE ENTIRE LENGTH 250.119 2. USE APPROVED FITTING WITH LB 110.3 -- CHASE NIPPLE NOT ALLOWED. 3. WHERE IS AC SERVICE WARNING LABEL - NOTE E 4. NEED METER SOCKET OPENED TO VERIFY CONNECTIONS AND TERMINATIONS. 5. PROPERLY GROUND JUNCTION BOXES - 3/4 OF A TURN UNDER GROUND SCREW. 6. MODULE ARRAYS NOT MOUNTED AS PER PLANS. 7. WHERE IS #8 CONDUCTOR TO SYSTEM GROUND ELECTRODE AS PER PLANS. |