Permit: T06CM05441

Parcel: 11205019B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM05441

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/02/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HAVE OVERFILLED BOXES -- NEC 314.16
2. SECURE FIXTURES TO GRID -- NEC 300.11
3. SECURE MC CONNECTORS TO FIXTURES
4. MC TO BE STRAPPED WITHIN 12" OF TERMINATIONS -
NEC 330.30C
5. SEAL UNUSED OPENINGS IN DISCONNECTS/BOXES -
NEC 314.17A
6. CHECK TO MAKE SURE LIGHTING TRANSFORMER IS CORRECTLY MOUNTED - PROVIDE PAPERWORK -- NEC 110.3
7. USE SINGLE MC CONNECTOR WHERE YOU HAVE SINGLE MC
NEC 300
8. SUPPORT WIRE FOR FIXTURES/EQUIPMENT NEED TO BE SEPARATE FROM GRID SUPPORT, CONNECTED AT OPPOSITE ENDS/CORNERS OF FIXTURES AND SECURE @ BOTH ENDS
NEC 300.11
9. AIR HANDLER DISCONNECTS TO BE ACCESSIBLE - NEC 110

REMOVE OLD WIRING IN CEILING
12/29/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) FINISH CEILING WIRING
2) HAVE CEILING OPEN FOR INSPECTION (REMOVE TILES)
12/27/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) CHECK METER BOND