Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM05441
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/02/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OVERFILLED BOXES -- NEC 314.16 2. SECURE FIXTURES TO GRID -- NEC 300.11 3. SECURE MC CONNECTORS TO FIXTURES 4. MC TO BE STRAPPED WITHIN 12" OF TERMINATIONS - NEC 330.30C 5. SEAL UNUSED OPENINGS IN DISCONNECTS/BOXES - NEC 314.17A 6. CHECK TO MAKE SURE LIGHTING TRANSFORMER IS CORRECTLY MOUNTED - PROVIDE PAPERWORK -- NEC 110.3 7. USE SINGLE MC CONNECTOR WHERE YOU HAVE SINGLE MC NEC 300 8. SUPPORT WIRE FOR FIXTURES/EQUIPMENT NEED TO BE SEPARATE FROM GRID SUPPORT, CONNECTED AT OPPOSITE ENDS/CORNERS OF FIXTURES AND SECURE @ BOTH ENDS NEC 300.11 9. AIR HANDLER DISCONNECTS TO BE ACCESSIBLE - NEC 110 REMOVE OLD WIRING IN CEILING |
|
| 12/29/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FINISH CEILING WIRING 2) HAVE CEILING OPEN FOR INSPECTION (REMOVE TILES) |
|
| 12/27/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CHECK METER BOND |