Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/28/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION ONLY 1. WORK IS NOT SHOWN ON PLAN, EQUIPMENT NOT SHOWN ON PLAN - REVISE PLANS TO SHOW ACCURATE AS BUILT 2. PANEL DIRECTORIES TO BE CORRECT 3. FAN COILS REQUIRE DISCONNECTING MEANS - NEC 440.14 |
|
| 11/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT PER PLAN 2. CEILING/EQUIPMENT TO BE ACCESSIBLE FOR INSPECTION |
|
| 11/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ELECTRICIAN TO BE ON SITE TO OPEN EQUIPMENT FOR INSPECTION |