Permit: T06CM05433

Parcel: 10612017G


Addresses:

1785 W PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/18/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/16/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/12/2007 ELECTRIC - INTERMEDIATE Partial Approval OK SODA FOUNTAIN AREA
BEFORE HRS. INSP. PAID CK 023047 $216.00
CHAD -- 481-8864
04/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR CABINET AREA
1. HAVE OPEN HOLES IN BOXES -- NEC 110
2. HAVE OVERFILLED BOXES -- NEC 314.16
3. MISSING J-BOX COVERS -- NEC 110
4. EQUIPMENT GROUND UNDERSIZED -- NEC 250.122
5. CKTS NOT IDENTIFIED IN PANEL DIRECTORY -- NEC 408.4
6. EMT NOT PROPERLY SECURED -- NEC 358.30