Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/16/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | OK SODA FOUNTAIN AREA BEFORE HRS. INSP. PAID CK 023047 $216.00 CHAD -- 481-8864 |
|
| 04/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR CABINET AREA 1. HAVE OPEN HOLES IN BOXES -- NEC 110 2. HAVE OVERFILLED BOXES -- NEC 314.16 3. MISSING J-BOX COVERS -- NEC 110 4. EQUIPMENT GROUND UNDERSIZED -- NEC 250.122 5. CKTS NOT IDENTIFIED IN PANEL DIRECTORY -- NEC 408.4 6. EMT NOT PROPERLY SECURED -- NEC 358.30 |