Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 02/06/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* USE PROPERLY SIZED CLAMPS FOR GROUND RODS-NEC 110.3 B 2) SERVICE RISERS BONDING CONDUCTOR IS UNDERSIZED-NEC 250.102 C 3) ARRANGE BONDING CONDUCTORS SO THEY DO NOT HAVE OBJECTIONABLE CURRENT-NEC 250.6 4) SERVICE LATERAL WILL NEED WARNING RIBBON NEC 305 D3 5) INSTALL ADDRESS ON SERVICE 6) IDENTIFY ALL SERVICE DISCONNECTS-NEC 230.70 B 7) BONDING CONDUCTORS FOR GUTTER NIPPLES UNDERSIZED-NEC 250.102 L 8) TIGHTEN ALL CONNECTIONS 9) BOND ALL METAL PIPING TO SERVICE-NEC 250.104 10) STRAP GROUNDING ELECTRODE CONDUCTOR PVC INTO CT CAN |