Permit: T06CM05433

Parcel: 10612017G


Addresses:

1785 W PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
02/09/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
02/06/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE PROPERLY SIZED CLAMPS FOR GROUND RODS-NEC 110.3 B
2) SERVICE RISERS BONDING CONDUCTOR IS UNDERSIZED-NEC 250.102 C
3) ARRANGE BONDING CONDUCTORS SO THEY DO NOT HAVE OBJECTIONABLE CURRENT-NEC 250.6
4) SERVICE LATERAL WILL NEED WARNING RIBBON NEC 305 D3
5) INSTALL ADDRESS ON SERVICE
6) IDENTIFY ALL SERVICE DISCONNECTS-NEC 230.70 B
7) BONDING CONDUCTORS FOR GUTTER NIPPLES UNDERSIZED-NEC 250.102 L
8) TIGHTEN ALL CONNECTIONS
9) BOND ALL METAL PIPING TO SERVICE-NEC 250.104
10) STRAP GROUNDING ELECTRODE CONDUCTOR PVC INTO CT CAN