Permit: T06CM05421

Parcel: 124161020


Addresses:

1301 S TYNDALL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EM. LIGHTING NOT CIRCUITED PER PLAN MUST COMPLY
WITH 700.16 NEC
2. PROVIDE LETTER FROM ARCHITECT FOR SP.TOGGLE SWITCHES IN LIEU OF DISCONNECTS FOR COOLERS.
10/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL SCHEDULES NOT IN
2. NIGHT LIGHTS, EM LIGHTS NOT WORKING AND NOT CIRCUITED PER PLAN
3. INSTALL COMBINATION STARTER OR STARTER WITH DISCONNECT (FUSED) FOR COOLERS, SEE PLANS.
4. PUMPS TO HAVE INSTATS PER PLAN (COOLERS)