Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EM. LIGHTING NOT CIRCUITED PER PLAN MUST COMPLY WITH 700.16 NEC 2. PROVIDE LETTER FROM ARCHITECT FOR SP.TOGGLE SWITCHES IN LIEU OF DISCONNECTS FOR COOLERS. |
|
| 10/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL SCHEDULES NOT IN 2. NIGHT LIGHTS, EM LIGHTS NOT WORKING AND NOT CIRCUITED PER PLAN 3. INSTALL COMBINATION STARTER OR STARTER WITH DISCONNECT (FUSED) FOR COOLERS, SEE PLANS. 4. PUMPS TO HAVE INSTATS PER PLAN (COOLERS) |