Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. BONDING REQUIRED AT SERVICE PER 250.66 AND 250.92 2. BUSHINGS REQUIRED IN GUTTER PER 300.4 NEC 3. OK EXTERIOR WALLS |
|
| 10/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* USE NAIL PLATES AT MC THRU SHALLOW STUDS OR INSTALL MC BEHIND STUDS. EXTERIOR WALLS. |
|
| 09/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LIDS OFFICE AREA |