Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/29/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OVER NOTCHED STUDS FOR LET-INS IN GARAGE NORTH WALL 2) DRAFT STOP 2ND FLOOR TUBS AT P-TRAPS 3) OVER NOTCHED EXTERIOR 2 X 4 BEARING WALLS UPSTAIRS 4) NAIL OFF UPSTAIRS SHEAR PANEL SOLE PLATES TO PLAN 5) SEAL GAS LINE AT REAR OF HOUSE 6) BLOCK MISSING IN SHEARWALL OF KITCHEN GAS LINE CAVITY 7) SEAL AROUND PENETRATIONS IN DRAFT STOP OF FLOOR TRUSSES 8) DRAFT STOP PENETRATION IN PLUMBING CHASE ABOVE MAIN FLOOR TUB 9) LATTERAL BRACE NEEDED IN RAFTERS ABOVE MECHANICAL 10) BANG PLATES OVER WIRES MASTER BEDROOM WEST WALL 11) BANG PLATE NEEDED NORTHEAST BEDROOM NORTH WALL 12) SUPPORT DRAIN LINE ABOVE MAIN FLOOR PANTRY 13) PLUMBING PLAN CORRECTED 14) H3 CLIPS NEEDED PATIO ROOF |