Permit: T06CM05407

Parcel: 115061660


Addresses:

1800 N ORACLE RD

Inspection Status: Approved

Inspection History: PLUMBING - PRE SLAB

Date Description Inspector Results Comments
04/03/2007 PLUMBING - PRE SLAB Approved IVRS - Inspection :*
OK FOR CONCRETE
03/14/2007 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
G.T OK
OK TO COVER UNDERGROUND
03/12/2007 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1. OK TO COVER UNDERGROUND
2. ABS S1 X S1 REDUCERS AT G.T NOT LISTED
TO SOLVENT CEMENT TO THREADED FITTING.
03/07/2007 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
OK TO COVER ALL AREAS EXCEPT GREASE TRAP OUTSIDE
1. STILL NO VENT ON GREASE TRAP
2. PROVIDE LISTING FOR 4" FIPX SL FITTINGS
3. CORRECT BACK PITCHED SECTIONS

2" WASTE LINES FOR FLOOR DRAINS/SINKS
HORIZONTAL VENTING BELOW FLOOD RIM LIMITED TO STRUCTURAL CONDITIONS, NO SUCH CONDITION EXISTS
PLUMB CONVENTIONALLY
03/02/2007 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
1. HORIZONTAL VENTING BELOW THE FLOOD RIM OF THE FIXTURE IS ALLOWED ONLY DUE TO STRUCTURAL CONDITIONS
2. NO VENT ON GREASE TRAP
3. UNPROTECTED STEEL FITTINGS BELOW GRADE NOT PERMITTED.
4. BLAKE TEE NOT LISTED TO BE USED IN A HORIZONTAL POSITION.