Inspection Status: Approved
Inspection History: PLUMBING - PRE SLAB
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2007 | PLUMBING - PRE SLAB | Approved | IVRS - Inspection :* OK FOR CONCRETE |
|
| 03/14/2007 | PLUMBING - PRE SLAB | Partial Approval | IVRS - Inspection :* G.T OK OK TO COVER UNDERGROUND |
|
| 03/12/2007 | PLUMBING - PRE SLAB | Partial Approval | IVRS - Inspection :* 1. OK TO COVER UNDERGROUND 2. ABS S1 X S1 REDUCERS AT G.T NOT LISTED TO SOLVENT CEMENT TO THREADED FITTING. |
|
| 03/07/2007 | PLUMBING - PRE SLAB | Not ready for Inspection | IVRS - Inspection :* OK TO COVER ALL AREAS EXCEPT GREASE TRAP OUTSIDE 1. STILL NO VENT ON GREASE TRAP 2. PROVIDE LISTING FOR 4" FIPX SL FITTINGS 3. CORRECT BACK PITCHED SECTIONS 2" WASTE LINES FOR FLOOR DRAINS/SINKS HORIZONTAL VENTING BELOW FLOOD RIM LIMITED TO STRUCTURAL CONDITIONS, NO SUCH CONDITION EXISTS PLUMB CONVENTIONALLY |
|
| 03/02/2007 | PLUMBING - PRE SLAB | Not ready for Inspection | IVRS - Inspection :* 1. HORIZONTAL VENTING BELOW THE FLOOD RIM OF THE FIXTURE IS ALLOWED ONLY DUE TO STRUCTURAL CONDITIONS 2. NO VENT ON GREASE TRAP 3. UNPROTECTED STEEL FITTINGS BELOW GRADE NOT PERMITTED. 4. BLAKE TEE NOT LISTED TO BE USED IN A HORIZONTAL POSITION. |