Permit: T06CM05407

Parcel: 115061660


Addresses:

1800 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT GROUND FOR AC #4 DISCONNECT TO UNIT TO BE GREEN OR BARE ENTIRE LENGTH, ALSO, NEED TO PROPERLY IDENTIFY PHASE CONDUCTORS AT BOTH ENDS.
2. CONDENSING UNIT FOR WALK IN TO HAVE COVER REQUIRED BY MANUFACTURES INSTRUCTIONS - PROVIDE THAT MANUAL

THERE WILL BE A REINSPECTION FEE IF NOT CORRECT NEXT INSPECTION

3. HAVE BROKEN BREAKER BLANKS IN PANEL
10/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS FOR ROOFTOP TO BE COMPLETED (ALL) BEFORE YOU CALL FOR FINAL
10/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR INTERIOR
1. ALL 120V 20 AMP RECEPTACLES IN KITCHEN AREA TO BE GFI PROTECTED
2. NEED 20 @ FUSE @ DISPOSAL, INSTALL GFI COVER
3. REPLACE POWER CORD
4. INSTALL PROPERLY SIZED GROUND TO DISHWASHER
5. CLOSE UP SPACE CEILING RACEWAYS
6. IN USE COVERS @ BARS SINKS (2)
10/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP ONLY
1. PANEL DIRECTORY TO BE PROPERLY IDENTIFIED
2. IDENTIFY ROOFTOP DISCONNECTS/EQUIPMENT
3. WALK IN CONDENSOR UNIT TO HAVE WEATHERPROOF ENCLOSURE
4. DISCONNECTS TO HAVE MIN. 36" FRONT CLEARANCE
5. STRAP ALL FLEX WITHIN 12" OF BOXES
6. GROUND ALL DISCONNECTS/EQUIPMENT
7. LOADS TO ORIGINATE FROM PANELS PER PLAN
8. FINISH DEMO OF UNUSED EQUIPMENT ON ROOF
9. EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH

PARTIAL INSPECTION ONLY
INSPECTION TO CONTINUE INSIDE, REMOVE ALL OBSTACLES FOR INSPECTION - KITCHEN OCCUPIED BEFORE APPROVAL.