Permit: T06CM05402

Parcel: 107040130


Addresses:

2502 N DRAGOON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/15/2007 ELECTRIC - FINAL Approved
02/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ELECTRICIAN ON SITE FOR INSPECTION
02/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DO NOT CALL BEFORE READY
REINSPECTION FEE NEEDS TO PAID BEFORE YOU CALL IN FOR FINAL INSPECTION 850-1004
01/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LOADS DO NOT ORIGINATE FROM PANEL AS OUTLINED ON PLAN.
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED - NEC 408.4
3. NEED PROTECTIVE BUSHING #4 AND LARGER (FLEX INTO ROOFTOP UNITS) NEC 300.4F

NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL
01/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL PROPERLY IDENTIFIED PANEL DIRECTORY'S
NEC 408.4
2. LOADS ORIGINATE FROM PANEL "M" INSTEAD OF "L2" AS OUTLINED ON PLAN? MAKE SURE LOADS ORIGINATE PER PLAN AND DIRECTORY'S ARE CORRECTLY IDENTIFIED.
3. NEED PROTECTIVE BUSHING FOR #4 AND LARGER CONDUCTOR - 300.4 F
4. IDENTIFY NAMEPLATES ON ROOFTOP UNITS AS TO IF THEY DO OR DON'T HAVE HEAT STRIPS INSTALLED, UNITS APPEAR TO BE OVERFUSED. ALSO, IDENTIFY DISCONNECTS WITH METHOD SUITABLE FOR ENVIRONMENT, NOT JUST A MARKER, ALSO, HAVE SEVERAL LOOSE FITTINGS FOR RACEWAYS AND EMT NOT ALL THE WAY IN FITTING. STILL NEED TO CHECK EMERGENCY LIGHTING.