Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/02/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING TO BE ON SAME CKT FOR LIGHTING IN THAT AREA -- NEC 700.12E 2. HAVE OVERFILLED BOXES -- NEC 314.16 3. SEAL UNUSED OPENINGS IN BOXES -- NEC 314.17 4. USE EQUIPMENT GROUND TO GROUND ALL BOXES -- NEC 250 5. STRAP EMT WITHIN 36" OF BOXES -- NEC 358.30 6. CEILING GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT ELECTRICAL EQUIPMENT -- NEC 300.11 7. FINISH ALL CEILING WIRING 8. SECURE FIXTURES TO GRID -- NEC 110.13, 300.11 9. SECURE/SUPPORT MC PROPERLY -- NEC 330.30 |