Permit: T06CM05402

Parcel: 107040130


Addresses:

2502 N DRAGOON ST

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/19/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/02/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING TO BE ON SAME CKT FOR LIGHTING IN THAT AREA -- NEC 700.12E
2. HAVE OVERFILLED BOXES -- NEC 314.16
3. SEAL UNUSED OPENINGS IN BOXES -- NEC 314.17
4. USE EQUIPMENT GROUND TO GROUND ALL BOXES -- NEC 250
5. STRAP EMT WITHIN 36" OF BOXES -- NEC 358.30
6. CEILING GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT ELECTRICAL EQUIPMENT -- NEC 300.11
7. FINISH ALL CEILING WIRING
8. SECURE FIXTURES TO GRID -- NEC 110.13, 300.11
9. SECURE/SUPPORT MC PROPERLY -- NEC 330.30