Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05396
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/19/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* FINISH WORK |
|
12/13/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL ROMEX INSTALLED W/O PERMITS OR INSPECTION ALL LOOSE ROMEX -- OK TO LEAVE NORTHSIDE WALLS WITH PROPERLY INSTALLED ROMEX. 2. SUPPORT VDV CABLES |
|
12/11/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE PROVIDE VERIFICATION OF ROMEX USE ROMEX WAS NOT ALLOWED IN THIS TYPE OF CONST. PROVIDE SUPPORT FOR VDV CABELING. 2. CORRECT WIRING TO CONDUIT OR MC CABLE USE. |
|
12/05/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW WIRING BOTH NM & MC APPEAR TO HAVE BEEN INSTALLED. PLEASE PROVIDE LAST PERMITTED PLANS AND INSPECTION REPORTS TO VERIFY WHAT HAS BEEN INSTALLED WITHOUT INSPECTIONS. 2. SUPPORT VDV CABELING AS PER 725.3 & 6 800.3 & 6 |
|
12/01/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OPEN AREA FOR INSPECTION 2. CORD NOT ALLOWED TO PASS THROUGH WALL |