Permit: T06CM05395

Parcel: 123020830


Addresses:

2540 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/26/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/28/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL A HAMMER ARRESTOR FOR COLD WATER BRANCH SERVING URINALS.
ALL RISERS HAVE CLEANOUTS. ALL CLEANOUTS WILL REQUIRE ACCESS.
RELOCATION OF WATER SERVICE OK, EXCEPT DIELECTRIC UNION CANNOT BE CONCEALED UNDER WALK. EXTENT GALV TRANSITION TO AN ACCESSIBLE LOCATION.
03/27/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/15/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/13/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
POST ADDRESS ON BUILDING
03/08/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. INTERMEDIATE NOT READY
2. CALL FOR A ROUGH PLUMBING INSPECTION
3. REDLINES ON APPROVED PLANS DO SHOW THE ADDITION
OF 2 FLOOR DRAINS.
4. REDLINES DO NOT SHOW DELETED WC OR HORIZONTAL VENTING.
5. ALSO, WASTE FOR MOP SINK NOT SIZED PER PLAN IT APPEARS THAT PLUMBER MAY INTEND TO WET VENT HORIZONTAL 2" WC VENT, THIS WOULD NOT BE ACCEPTED.
6. PROVIDE A PLAN REVISION SHOWING ACTUAL INSTALLATIONS, RED LINES WILL BE PARTIALLY ACCEPTED.
03/02/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
ADD ROUGH SOIL TO PERMIT
NOT INSTALLED PER PLAN
PLAN DRAWN IN ERROR
FLOOR DRAINS REQUIRED PER SEC 412.2.1