Permit: T06CM05395

Parcel: 123020830


Addresses:

2540 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EMERGENCY LIGHTING TO BE ENERGIZED BY CKT FEEDING NORMAL LIGHTING IN THAT AREA - SEE NEC 700.12
2. PROVIDE LETTER FOR CHANGE IN EMERGENCY LIGHTING
3. PROVIDE ROOFTOP SERVICE RECEPTACLE.
05/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
NEED ELECTRICIAN ON SITE TO OPEN EQUIPMENT
MAKE SURE WIRING IS PER PLAN