Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EMERGENCY LIGHTING TO BE ENERGIZED BY CKT FEEDING NORMAL LIGHTING IN THAT AREA - SEE NEC 700.12 2. PROVIDE LETTER FOR CHANGE IN EMERGENCY LIGHTING 3. PROVIDE ROOFTOP SERVICE RECEPTACLE. |
|
| 05/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS NEED ELECTRICIAN ON SITE TO OPEN EQUIPMENT MAKE SURE WIRING IS PER PLAN |