Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) OPEN CEILING FOR INSPECTION 2) USE APPROVED GROUNDING METHODS AT BOXES 3) OVER FILLED BOXES 4) NEED ALL PLANS ON SITE 5) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 6) GROUND ENCLOSURE FOR LIGHTING CONTROL 7) SIGN CIRCUIT TO BE PER 600.5 |