Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM05388
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 2 ABS RISERS AT SW CORNER DO NOT HAVE FOAM PROTECTION. PROTECT PRIOR TO CONCRETE. |
|
01/02/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* DWV OK TO COVER |
|
12/29/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BACK PITCH PRESENT IN 2 PLACES, LESS THAN 1/4" PRESENT IN 4 PLACES 2) PROVIDE UNIFORM SLOPE THROUGHOUT WITH NOT LESS THAN 1/4" PER FOOT. USE GRADE LEVEL |
|
12/22/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROCKS LARGER THAN 3/4" TOUCHING PIPE INSPECTION STOPPED |
|
12/19/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO ROCKS OR CHUNKS LARGER THAN 3/4" 2. NO FERNCO COUPLINGS INSIDE BUILDING -- USE MISSION COUPLINGS. 3. MIN. TRAP ARM DISTANCE IS 2X PIPE DIAMETER 4. PROVIDE 1/4" PER FOOT SLOPE IN ALL AREAS. 5. SUPPORT HORIZONTAL VENT BETTER 6. MISSING P-6 REDLINE ANY CHANGES INSTALL PER PLAN. |
|
12/13/2006 | PLUMBING - ROUGH, SOIL | Cancelled | IVRS - RI canceled |