Permit: T06CM05388

Parcel: 11005314J

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM05388

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
2 ABS RISERS AT SW CORNER DO NOT HAVE FOAM PROTECTION. PROTECT PRIOR TO CONCRETE.
01/02/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
DWV OK TO COVER
12/29/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BACK PITCH PRESENT IN 2 PLACES, LESS THAN 1/4" PRESENT IN 4 PLACES
2) PROVIDE UNIFORM SLOPE THROUGHOUT WITH NOT LESS THAN 1/4" PER FOOT. USE GRADE LEVEL
12/22/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROCKS LARGER THAN 3/4"
TOUCHING PIPE
INSPECTION STOPPED
12/19/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO ROCKS OR CHUNKS LARGER THAN 3/4"
2. NO FERNCO COUPLINGS INSIDE BUILDING -- USE MISSION COUPLINGS.
3. MIN. TRAP ARM DISTANCE IS 2X PIPE DIAMETER
4. PROVIDE 1/4" PER FOOT SLOPE IN ALL AREAS.
5. SUPPORT HORIZONTAL VENT BETTER
6. MISSING P-6 REDLINE ANY CHANGES INSTALL PER PLAN.
12/13/2006 PLUMBING - ROUGH, SOIL Cancelled IVRS - RI canceled