Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COVENANT RECEPTACLES TO BE GFCI PROTECTED IN KITCHEN -- 210.8 2. SEAL WALKIN BOX SWITCH CONDUIT PER 300.7 |
|
| 03/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP POWER FOR TEST SUBJECT TO POSTING OF BOND |