Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
| 03/26/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BACKING STILL MISSING UNIT #5 TERMINATE DRYER VENT INTO SIDE WALL AND PROVIDE BACKING FOR EXHAUST TERMINATION - SUPPLY TO BEDROOM |
|
| 03/25/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DRYER VENT IS NOT INSIDE WALL AND IS MISSING TAPE ON FIRST JOINT. 2. EXHAUST FLEX DAMAGED AT FAN 3. BACKING MISSING ON BEDROOM SUPPLY BOX |
|
| 03/24/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/23/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT TERMINATE DRYER VENT INTO AN OVAL FURNACE FLUE OTHER CORRECTIONS HAVE NOT BEEN MADE. |
|
| 02/26/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOOR LOCKED |
|
| 12/03/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/08/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO CONDENSATE DRAIN EXHAUST VENT NOT SCREWED - NOT SECURED NO DRYER VENT SUPPLY BOXES NOT TERMINATED CORRECTLY REFRIGERATION LINE MISSING INSULATION FROM UNIT BELOW |