Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05319
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO SCREWS IN PLASTIC BOX 2. BATHROOM RECEPT TO BE DEDICATED 20a CIRCUIT NO OTHER OUTLETS TO BE ON CIRCUIT 3. WATER LINE UNDER PANEL IN EQUIPMENT DEDICATED SPACE NEEDS TO BE MOVED 4. STRAP SER CABLE IN ATTIC EVERY 54" |
|
12/10/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1. NEED TO HAVE APPROVED PLANS ON SITE & PREVIOUS INSPECTION REPORTS 2. UNNECESSARY INSPECTION REQUESTS WILL RESULT IN REFEE |
|
12/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NO PANEL FEEDERS |