Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05311
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
11/24/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) WATER HEATER VENT CRIMPED END BACKWARDS AND HAS NO SLOPE 2) DO NOT NOTCH THE REDUCER FROM FURNACE TO FIT INTO VENT TEE 3) NEED POWER TO CHECK DRYER AND EXHAUST VENTS |
|
11/17/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE FUSES 2) PROVIDE PROTECTIVE COATING ON EXPOSED ARMAFLEX 3) SUPPORT REFER LINES AND ELECTRIC CONDUITS 4) PROVIDE CLEARANCE TO COMBUSTIBLES AT FURNACE VENT CONNECTOR 5) SECURE ANGLE IRON FRAMES 6) PROVIDE PROPER VENT CAPS ON FLUE PIPES EXTEND 3' ABOVE COMBUSTION AIR INTAKE |
|
12/04/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* ON FINAL BE SURE ALL DRYER VENT DAMPERS WORK PROPERLY -- OK FOR SHEETROCK |